Messana Radiant Cooling Test Reports
RAY MAGIC PANELS

ASTM C578
Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation

ASTM E84 EPS
84-10 Standard Method of Test for Surface Burning Characteristics of Building Materials (EPS ONLY)
Comparable to UL 723, ANSI/NFPA No. 255, and UBC No. 8-1

ASTM E84 Gypsumboard Side
E84-10 Standard Method of Test for Surface Burning Characteristics of Building Materials (Ray Magic Panel)
Comparable to UL 723, ANSI/NFPA No. 255, and UBC No. 8-1
Test Results
Ray Magic radiant gyspsum panel with EPS Foam, having a density of 1.82 pcf, met the density, thermal resistance, flexural and compressive strength requirements of ASTM C 578-10 for Type IX foam
Ray Magic EPS R-Value = 6.433 Fxft2xh/Btu x 1.5″ = 9.65 R-Value
Test Results
Flame Spread 5, Smoke Developed 35, Class A
Test Results
Flame Spread 0, Smoke Developed 5, Class A

ASTM C1396
ASTM C1396/C1396M-13 Standard Specification for Gypsum Board

Class 1 Fire Resistance UNI 8457 9174
Resistance to fire test (UNI 8457/9174) and Fire classification of construction products and building elements European Standard EN 13501-1

EN 14240 Cooling
European Standard EN 14240 test conditions and methods for the determination of the cooling capacity of chilled ceilings and other extended chilled surfaces
Test Results
Ray Magic radiant gypsum board meets the requirements of ASTM C1396/C1396M-13 for Gypsum board
Test Results
Ray Magic panel is classified as a class 1 product

EN 14037 Heating
European Standard EN 14240 test conditions and methods for the determination of the heating capacity of hot ceilings and other extended hot surfaces